Room-by-room surface finish specifications. Every floor, wall surface, ceiling tile, and bass trap — material, product, thickness, and acoustic rating.
NW quadrant — deadest room, voiceover and narration recording
| Surface | Material / Assembly | Product | Thickness | Rating | Notes |
|---|---|---|---|---|---|
| Floor | Float floor + carpet | Sylomer SR 28 pads + 2×18mm T&G plywood + carpet finish | ~150 mm total buildup | Isolation | 10 mm perimeter gap all sides, filled with acoustic sealant. Carpet on top of plywood. AC |
| Walls — All | 70% coverage — 50 mm rockwool absorption panels, fabric wrapped | Rockwool RWA45 (45 kg/m³) core, acoustically transparent fabric cover | 50 mm panel + 25 mm air gap off wall face | 70% coverage | Panels on all four wall faces (incl. diagonal NW). 30% remaining wall is painted gypsum. AC |
| Walls — substrate | North: concrete + 25mm air gap + RSIC-1 clips + hat channel + 50mm rockwool + 2× gypsum | Knauf Soundshield Plus 15mm, Green Glue between layers | ~100 mm total treatment | STC 65 | North concrete wall (exterior). Do not breach air gap. AC |
| Walls — substrate | NW diagonal: concrete + 25 mm air gap + RSIC-V clips + hat channel + 50 mm rockwool + 2× gypsum | Knauf Soundshield Plus 15 mm | ~100 mm total treatment | STC 65 | Diagonal concrete wall (exterior). RSIC-V clips for angled geometry. AC |
| Walls — substrate | South (VO/Control partition): 2×12.5mm gypsum + 100mm studs + rockwool + 2×12.5mm gypsum | Knauf Standard 12.5mm both sides; Rockwool RWA45 cavity fill | 150 mm total | STC 53 | Includes observation window cutout — see DOOR-DETAILS for window spec. AC |
| Walls — substrate | East (Buffer Spine): 2×12.5mm gypsum + Green Glue + 100mm studs + rockwool + 2×12.5mm gypsum + Green Glue | Knauf Soundshield Plus; Green Glue Noiseproofing Compound | 150 mm total | STC 55 | Buffer spine face. Duct penetrations fully sealed with intumescent collars. AC |
| Ceiling tiles | Full coverage mineral wool ceiling tiles in exposed T-grid at 2.75 m FFL | Rockfon Sonar E 600×600mm | 20 mm tile | NRC 0.90 | 100% coverage. Fire rating A1 non-combustible. White (paintable). Armstrong Prelude 24mm T-grid. AC |
| Above-tile insulation | Rockwool batts laid on top of tiles — prevents plenum flanking | Rockwool ProRox SL 930 (100 mm), 40 kg/m³ | 100 mm batts | NRC 0.95 | Cut to 610×610 mm, butt joints, no gaps. Verify grid load capacity before installation. AC |
| Bass traps | Triangular corner-mounted absorption, floor to acoustic ceiling | Rockwool RWA45 (100 kg/m³) core, 300 mm triangular section, fabric wrapped | 300 mm leg (triangular) | 4 corners | Floor to ceiling (2.75 m) in all four room corners. Fabric: acoustically transparent. AC |
| Tuning curtain | Motorised ceiling-track curtain — RT60 tuning element | 450 g/m² acoustic velour, double-layered, 3.2 m² coverage. DC motor <20 dBA | Floor-to-ceiling drop (2.75 m) | Variable | Retracted = RT60 0.20 s. Deployed = RT60 0.27 s. Both within acceptance range. Motor between takes only. DEC |
SW quadrant — mixing and monitoring, trapezoid plan
| Surface | Material / Assembly | Product | Thickness | Rating | Notes |
|---|---|---|---|---|---|
| Floor | Float floor + carpet | Sylomer SR 28 pads + 2×18mm T&G plywood + carpet finish | ~150 mm total buildup | Isolation | 10 mm perimeter gap. Carpet finish — equipment must roll easily; choose low-pile. AC |
| Front Wall (North) | 50 mm rockwool absorption behind monitor positions | Rockwool RWA45 50 mm panels, fabric wrapped | 50 mm + air gap | Absorption | Full width behind monitors. Eliminates comb filtering at mix position. AC |
| Side Walls | First-reflection point panels — absorption at primary reflection zones | Rockwool RWA45 50 mm panels, fabric wrapped | 50 mm + air gap | Targeted | Locate using mirror method from mix position. Remaining side wall surfaces: painted gypsum. AC |
| Rear Wall (South) | QRD diffuser array | 80×80 cm QRD panels (N=7 sequence), MDF construction | 80×80 cm modules, depth per design | Diffusion | Full rear wall coverage. Eliminates flutter echo and rear wall reflection to mix position. AC |
| West Wall (Diagonal) | Concrete + RSIC-V clips + gypsum substrate; absorptive panels optional | Knauf Soundshield Plus 15 mm over RSIC-V system | ~100 mm total | STC 65 | Non-parallel geometry naturally diffuses modes. Exposed gypsum face acceptable — paint finish. DEC |
| East Wall (Buffer) | Buffer spine face — gypsum with Green Glue | Knauf Soundshield Plus 15 mm + Green Glue | 150 mm total (spine) | STC 55 | Paint finish. No treatment panels required on buffer face. AC |
| Ceiling tiles | 60% cloud coverage mineral wool tiles — remainder open plenum (grid present, no tile) | Rockfon Sonar E 600×600mm | 20 mm tile | NRC 0.90 | 60% fill in T-grid at 2.75 m FFL. Balance maintains liveness at high frequencies. A1 fire rating. AC |
| Above-tile insulation | Rockwool batts on all tiles (including non-tiled grid positions) | Rockwool ProRox SL 930 (100 mm) | 100 mm | NRC 0.95 | Laid on tiles; also placed on bare grid rails to prevent plenum flanking over partial-tiled ceiling. AC |
| Bass traps | Triangular corner-mounted, floor to ceiling | Rockwool RWA45 (100 kg/m³), 300 mm triangular section, fabric wrapped | 300 mm leg | 4 corners | All four room corners, full height 2.75 m. Critical for RT60 0.30–0.40 s target. AC |
NE quadrant — 3-camera green screen, podcast, live performance
| Surface | Material / Assembly | Product | Thickness | Rating | Notes |
|---|---|---|---|---|---|
| Floor | Float floor — NO carpet. Hard surface finish | Sylomer SR 28 pads + 2×18mm T&G plywood + smooth vinyl or sealed hardwood overlay | ~150 mm float + 3–8 mm finish | Hard surface | 10 mm perimeter gap maintained. Avoid thick rigid tiles that bridge float floor isolation. AC |
| Walls — Absorption (50%) | 50mm rockwool panels, fabric wrapped — distributed on all wall faces | Rockwool RWA45 (45 kg/m³) panels, acoustically transparent fabric | 50 mm + air gap | 50% coverage | Evenly distributed around all walls. No single wall to be 100% absorptive. AC |
| Walls — Diffusion (20%) | QRD or skyline diffuser panels | MDF QRD panels, natural or painted finish | Per design depth | 20% coverage | Placed at primary reflection zones opposite absorptive panels. Maintains liveness and spatial feel for video. AC |
| Walls — Reflective (30%) | Painted gypsum — bare finish | Knauf Soundshield Plus face; standard wall paint | Gypsum face (no treatment) | 30% of area | Remaining wall area. Colour per client preference. Do not add mass (no tile cladding). DEC |
| North Wall (exterior) | Concrete + RSIC-1 clips + hat channel + 50mm rockwool + 2× gypsum | Knauf Soundshield Plus 15 mm | ~100 mm treatment | STC 65 | Exterior concrete. Treatment panels applied on top of gypsum face. AC |
| East Wall (server room) | 100mm existing air gap + 2×16mm gypsum + Green Glue + 70mm studs + rockwool + 2×16mm gypsum + Green Glue | Knauf Soundshield Plus; Green Glue CLD | 16 cm new-build; 234mm total incl. existing gap | STC 62 | Do NOT fill existing 100mm air gap — critical decoupling from server noise (B313). AC |
| Ceiling tiles | 80% coverage mineral wool tiles — impact-resistant grade for rigging loads | Rockfon Sonar E 600×600mm | 20 mm tile | NRC 0.90 | 80% fill in T-grid at 2.75 m FFL. A2-s1,d0 fire rating. Impact-resistant for lighting/camera rigging. AC |
| Above-tile insulation | Rockwool batts on tiles | Rockwool ProRox SL 930 (100 mm) | 100 mm | NRC 0.95 | 610×610mm cut batts, butt joints, no gaps. Verify grid load with 20% open tiles accounted for. AC |
| Bass traps | Triangular corner-mounted, floor to ceiling | Rockwool RWA45 (100 kg/m³), 300 mm triangular section, fabric wrapped | 300 mm leg | 4 corners | All four room corners, full height 2.75 m. Fabric colour: client choice (acoustically transparent). AC |
SE quadrant — post-production workstations, also serves as circulation corridor
| Surface | Material / Assembly | Product | Thickness | Rating | Notes |
|---|---|---|---|---|---|
| Floor | Float floor + carpet | Sylomer SR 28 pads + 2×18mm T&G plywood + carpet finish | ~150 mm total buildup | Isolation | 10 mm perimeter gap. Carpet reduces footfall noise — important as this room is circulation corridor. AC |
| Walls (30% coverage) | Minimal absorption panels — only 30% of wall area treated | Rockwool RWA45 50 mm panels, fabric wrapped | 50 mm + air gap | 30% coverage | Concentrate at workstation positions to reduce reflections at monitor listening points. AC |
| South Wall (exterior) | Rebuilt south wall: 2×12.5mm gypsum + 100mm studs + rockwool + 2×12.5mm gypsum | Knauf Standard 12.5mm; Rockwool RWA45 100mm cavity | 150 mm total | STC 50 | Contains D1 main entry door (STC 50) — door is weakest link in this wall. Paint finish. AC |
| East Wall (server room) | 100mm existing air gap + new stud frame + gypsum + Green Glue | Knauf Soundshield Plus; Green Glue CLD | 16 cm new-build; 234mm total | STC 62 | Do NOT fill existing air gap. Paint or panel finish on interior face. AC |
| North Wall (Video Studio partition) | 12.5mm gypsum + 70mm studs + rockwool + 12.5mm gypsum | Knauf Standard 12.5mm; Rockwool RWA45 cavity | ~95 mm (nominal 100mm incl. tracks) | STC 40 | Partition to Video Studio. Contains D4 door (STC 40). Match panel finish to room. AC |
| West Wall (Buffer Spine) | Buffer spine east face — gypsum + Green Glue | Knauf Soundshield Plus; Green Glue | 150 mm (spine total) | STC 55 | Contains D2 door to Control Room. Paint or light treatment finish. AC |
| Ceiling tiles | Standard office-grade mineral wool tiles — full coverage | Armstrong Ultima+ 600×600mm | 19 mm tile | NRC 0.70 | 100% coverage in T-grid at 2.75 m FFL. Class A fire rating. Standard white. AC |
| Above-tile insulation | Rockwool batts on tiles | Rockwool ProRox SL 930 (100 mm) | 100 mm | NRC 0.95 | 610×610mm cut batts. Prevents plenum flanking from adjacent spaces. AC |
| Bass traps | None required | — | — | N/A | NC-35 tolerance is sufficient without corner bass traps. Omit to save cost. Low-frequency modal control not critical in this room. DEC |