Electrical & Data Infrastructure BOM

Power circuits, outlet positions, and data cabling for the MediaVerse Studio Complex. All specifications from ACOUSTIC-CONSTANTS.js Single Source of Truth.

BUILDER CUSTOMIZATION GUIDE — ELECTRICAL BOM

CUSTOMIZABLE — Receptacle brand and color may be substituted if the replacement meets or exceeds the specified current rating (16A) and grounding requirements. Cable brand may vary if Cat6A S/FTP rating and plenum certification are maintained. Conduit routing paths may be adjusted to avoid structural conflicts, provided separation from power is maintained (600mm for audio, 300mm for data).

DO NOT ALTER — Isolated ground circuit design (no shared neutrals), back-to-back box prohibition (600mm offset minimum), putty pad requirement on all boxes, steel box requirement for STC-rated walls, conduit seal specifications at acoustic boundaries. These values are acoustically engineered and changing any of them invalidates the wall STC ratings.

Panel Specifications

Power Circuits

Four dedicated circuits with isolated grounds. Each circuit has its own home run to the panel.

Circuit ID Room Breaker Receptacle Load Current Utilization Devices

Total Power Load

Outlet Locations

Power and data outlet positions per room. Coordinates in SVG space (cm from zone origin).

Data Cabling

Acoustic Rules

Critical acoustic requirements for electrical installations in STC-rated walls.

Lighting, Tally & Stagebox Components

Additional electrical components added in Phase L for lighting infrastructure, recording tally lights, and inter-room stagebox wiring.

ItemQtySpecRoomCircuitNotes
Lighting Fixtures
LED Panel (overhead)1200W max, 2700KVO LiveAV-02Dimmable, ceiling mount
Music Stand Clip Light15W, 2700KVO LiveAV-02Clamp-on LED
LED Panel (bias lighting)1~40W, 3200KControl RoomAV-01Dimmable, ceiling mount
Godox LE300Bi3300W bi-color LED, 3200-5600KVideo StudioAV-03Key/fill/rim lights
Godox LE200Bi2200W bi-color LED, 3200-5600KVideo StudioAV-03Background/accent
Softboxes (60x90cm)3Bowens mountVideo StudioModifier for LE300Bi
LED Panel (task lighting)2~30W each, 4000KEditing SuiteAV-04Dimmable, ceiling mount
Emergency LED Strip15W, 4000K, battery-backedBuffer SpineHouseAutomatic on power failure
0-10V Dimmer Switch4Lutron or equivalentAll roomsOne per room (excl. buffer)
DMX Controller1DMX512, 12-channel minVideo StudioControls all studio lights
Recording Tally Lights
LED Tally Light (red)212V DC, 5W eachBuffer SpineAV-01/AV-03TALLY-01 above D2, TALLY-02 above D4
12V DC PSU212V 1A regulatedCR / StudioPowers tally from inside room
Toggle Switch (panel-mount)2SPST, 12V DCCR / StudioManual tally activation
Stagebox Connectors & Wiring
Neutrik NC3MD-L-1 (XLR-M panel)8D-series panel mountVO Live / Studio4 per talent-side panel (SB-01 + SB-02)
Neutrik NC3FD-L-1 (XLR-F panel)8D-series panel mountControl Room4 per CR-side panel (SB-01 + SB-02)
Neutrik NJ3FP6C (TRS-F panel)86.35mm D-series panelVO Live / Studio4 per talent-side panel
Neutrik NP3X (TRS-M panel)86.35mm D-series panelControl Room4 per CR-side panel
Neutrik NE8FDX-P6 (Cat6A panel)4Ethercon D-seriesAll stagebox1 per side per stagebox
Neutrik NBNC75BFG7 (BNC panel)275Ω BNC D-seriesSB-02 onlySDI camera return, 1 per side
Mogami W2534 (bulk, per m)50Quad-core mic cableConduits8 XLR runs × ~6m avg
Mogami W2549 (bulk, per m)50Balanced line cableConduits8 TRS runs × ~6m avg
Belden 1694A (bulk, per m)15RG-6 SDI coaxSB-02 conduit1 SDI run through buffer spine
32mm Steel Conduit2Acoustically sealedPartitionsSB-01 + SB-02 through walls
Fire-rated Putty Pads4IntumescentConduit endsBoth ends of both conduits
Stagebox Faceplates (8-port D)41U Neutrik D-seriesAll positions2 sides × 2 stageboxes
Floor Box (CR-FB)
Flush-mount Floor Box1Brass lid, 4-gangControl RoomAV-01Under mixing desk, x:100 y:300
Schuko Socket (IG)216A isolated groundCR Floor BoxAV-01Audio interface + monitor power
Cat6A Keystone Jack2Shielded, snap-inCR Floor BoxLAN + audio network

Outlet Summary

Critical Notes

Critical Installation Requirements
  • Isolated ground circuits: Each circuit runs a separate equipment ground conductor back to the panel. No shared neutrals between circuits to prevent ground loops and electrical noise in audio equipment.
  • Back-to-back prohibition: No electrical boxes may be placed back-to-back across STC-rated walls. Maintain minimum 600mm horizontal offset between boxes on opposite sides of any acoustic partition.
  • Steel boxes only: Use heavy-gauge steel electrical boxes in all STC-rated walls. Plastic boxes do not meet acoustic mass requirements.
  • Putty pad coverage: Apply acoustic putty pads to all 5 exposed sides of every electrical box before installing in wall cavity.
  • Penetration sealing: All cable penetrations through acoustic walls must be sealed with Tremco acoustic sealant. Apply sealant wet, before cable pull.
  • Floor box coordination: Floor box conduit stub-ups installed DURING float floor construction (Phase 2) using liquidtight flexible conduit between slab and floating floor — rigid conduit bridges acoustic isolation. Coordinate with float floor sequence.
  • Wall box timing: All electrical boxes mount to studs DURING wall construction (Phases 3–4) while cavities are open, BEFORE gypsum closes. Never cut into finished acoustic walls.
Data Cabling Note

Cable separation (studio standard): power-to-audio 600mm minimum, power-to-data 300mm minimum on parallel runs. All crossings at 90° perpendicular only. Analog audio cables NEVER share conduit with digital (ethernet, DMX) or AC power. Use EMT (steel) conduit for EMI shielding. All data terminations tested to 500MHz before acceptance.